Sensepoint HT Sensor
The Sensepoint high temperature sensor has been designed for the detection of combustible gases in high temperature hazardous area locations. Typical applications include turbine enclosures and drying ovens used in solvent based printing and coating machines. These applications require a sensor that provides reliable and stable detection allowing low level alarm settings across a wide temperature range. Utilizing a specially matched pair of Sieger poison resistant combustible gas detection elements, the Sensepoint High Temperature Sensor has a very stable baseline allowing alarm trip points to be set as low as 5% LEL across a temperature range of -40°C to +150°C (-40°F to +302°F). The gas measuring range can be configured from 0-20% LEL up to 0-100% LEL depending on the type of controller used.
Availability: Commercially Available
Manufacturer |
| Honeywell Analytics |
Product Name |
| Sensepoint HT Sensor |
Detection Category |
| Chemical |
Detection Principle |
| Sensors; |
Detection Method |
| Electrochemical Detection ; |
Application |
| Emergency Response; Gas Analysis; |
Equipment Type |
| Sensor |
Product Synopsis |
| The Sensepoint high temperature sensor has been designed for the detection of combustible gases in high temperature hazardous area locations. Typical applications include turbine enclosures and drying ovens used in solvent based printing and coating machines. These applications require a sensor that provides reliable and stable detection allowing low level alarm settings across a wide temperature range. Utilizing a specially matched pair of Sieger poison resistant combustible gas detection elements, the Sensepoint High Temperature Sensor has a very stable baseline allowing alarm trip points to be set as low as 5% LEL across a temperature range of -40°C to +150°C (-40°F to +302°F). The gas measuring range can be configured from 0-20% LEL up to 0-100% LEL depending on the type of controller used. |
Availability |
| Commercially Available |
Technology Readiness Level (TRL) |
| 9 |
User Feedback Sources |
| Indifferent/No user feedback |
Dimensions |
| 1.7 x 2.3 in (42 x 58 mm) |
Weight |
| <1 lb.; 7.9 oz (225 g) |
Power Requirements |
| AC/DC Line Power; 0.7 W at 200 mA |
Transportability |
| Pocket Size |
Ruggedness |
| Extreme Temperatures/Humidity |
Operating Conditions |
| -55 to 150°C (-67 to 302°F); 75 to 110 kPa Operating Pressure; 20 to 90%RH |
Calibration Schedule |
| Yes |
Communications Interface |
| 3 wire mV bridge output |
Shelf Life |
| >5 years |
Other Chemical Targets |
| Combustible Gases |
Sample Introduction |
| Vapor/Gas |
Sensitivity/Detection Limits |
| %LEL |
Start Up Time (From Cold Start To Sample Ready) |
| 30 minutes |
Response Time (Sample Application To Output) |
| Continuous (<30 seconds); T(60)< 6 seconds, T(90)< 10 seconds |
Alarm Capability |
| Yes |
Software Control |
| Yes |
Training Required |
| <1 week training |
Manuals Available |
| Yes |